Modbus Integrator's Guide for the CXC HP | 2 - Using Modbus
Table 22. DC System Disconnects Data Points
Name Register Format
Disconnect: Disconnect Inhibit 02:Input Status Boolean
Disconnect: Disconnect Pending 02:Input Status Boolean
Disconnect: Disconnect Active 02:Input Status Boolean
Disconnect: Disconnect Open 02:Input Status Boolean
Disconnect: Manually Closed 02:Input Status Boolean
Disconnect: Manually Open 02:Input Status Boolean
Table 23. DC System Shunts Data Points
Name Register Format
Shunt/348: Current 04:Input Register 32-bit Floating Point
Table 24. DC System Current Transducer (CT) Data Points
Name Register Format
CT/397: Current 04:Input Register 32-bit Floating Point
Table 25. DC System Rectifiers Data Points
Name Register Format
CAN Serial Number 04:Input Register 32-bit Integer
AC Input Voltage 04:Input Register 32-bit Floating Point
Output Current 04:Input Register 32-bit Floating Point
Ambient Temperature 04:Input Register 32-bit Floating Point
Table 26. AMPS HP System Data Points
Name Register Format
T2S Comms Lost 02:Input Status Boolean
Page 28 0350114-J0 Rev G