Modbus Integrator's Guide for the CXC HP | 2 - Using Modbus
Table 22. DC System Disconnects Data Points
Name Register Format
Disconnect: Disconnect Inhibit 02:Input Status Boolean
Disconnect: Disconnect Pending 02:Input Status Boolean
Disconnect: Disconnect Active 02:Input Status Boolean
Disconnect: Disconnect Open 02:Input Status Boolean
Disconnect: Manually Closed 02:Input Status Boolean
Disconnect: Manually Open 02:Input Status Boolean
Table 23. DC System Shunts Data Points
Name Register Format
Shunt/348: Current 04:Input Register 32-bit Floating Point
Table 24. DC System Current Transducer (CT) Data Points
Name Register Format
CT/397: Current 04:Input Register 32-bit Floating Point
Table 25. DC System Rectifiers Data Points
Name Register Format
CAN Serial Number 04:Input Register 32-bit Integer
AC Input Voltage 04:Input Register 32-bit Floating Point
Output Current 04:Input Register 32-bit Floating Point
Ambient Temperature 04:Input Register 32-bit Floating Point
Table 26. AMPS HP System Data Points
Name Register Format
T2S Comms Lost 02:Input Status Boolean
Page 28 0350114-J0 Rev G

Table of Contents

Other manuals for Alpha Technologies Cordex CXC HP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Alpha Technologies Cordex CXC HP and is the answer not in the manual?

Alpha Technologies Cordex CXC HP Specifications

General IconGeneral
BrandAlpha Technologies
ModelCordex CXC HP
CategoryController
LanguageEnglish