EasyManua.ls Logo

Alpha ALPHA6000 Series - Page 102

Alpha ALPHA6000 Series
243 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Parameter Index
http://www.acdrive-china.com
102
Function
code
Function
Name
LCD
Display
Range of
settings
Default
Change
MODBUS
Address
Pd.02
Pre-overload
detection
Level
Pre-overloa
d detection
Level
20.0200.0%
160.0%
× 0E02
Pd.03
Pre-Overloa
d detection
time
Pre-Overlo
ad
detection
time
0.060.0s
60.0s
× 0E03
Pd.04
Current
amplitude
limit
Current
amplitude
limit
0:Invalid
1: Valid during
Acceleration
and
deceleration,
invalid in
constant
speed
Operation
2: Valid
1
0E04
Pd.05
Current
amplitude
limiting
level
Current
amplitude
limiting
level
Type G:80
180%
Type P:60
140%
G:150%
P:120%
0E05
Pd.06
Over-voltag
e at stall
function
selection
Over-volta
ge at stall
function
selection
0:Disabled (The
proposed
option, when
braking
resistor is
mounted)
1:Enabled
1
× 0E06
Pd.07
Over-voltag
e point at
stall
Over-volta
ge point at
stall
3004GB or
below:
110.0
150.0% (Bus
voltage)
35R5GB/37R5P
B or above:
120.0
150.0% (Bus
voltage)
220V:
120.0%
380V:
140.0%
× 0E07

Table of Contents

Related product manuals