Alstom MiCOM P54 Series - 2.4.5 Distance scheme BLOCKING (Distance option only); 2.4.6 Permissive overreach schemes current reversal guard (Distance option only); 2.4.7 Blocking scheme current reversal guard (Distance option only); 2.4.8 Aided DEF ground fault scheme - permissive overreach (Distance option only)

Alstom MiCOM P54 Series
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Application Notes P54x/EN AP/La4
MiCOM P543, P544, P545 & P546
(AP) 6-35
AP
2.4.5 Distance scheme BLOCKING (Distance option only)
To allow time for a blocking signal to arrive, a short time delay on aided tripping, “Dist dly”,
must be used, as follows:
Recommended Dly setting = Max. Signaling channel operating time + 1 power frequency
cycle.
This scheme is similar to that used in the LFZP Optimho, SHNB Micromho, LFZR, and
MiCOM P44x
(note 3)
distance relays. (Note 3: matches BOP Z2 mode in P441/442/444).
Send logic: Reverse Zone 4
Trip logic: Zone 2, plus Channel NOT Received, delayed by Tp
Note: Two variants of a Blocking scheme are provided, Blocking 1 and
Blocking 2. Both schemes operate identically, except that the reversal
guard timer location in the logic changes. Blocking 2 may sometimes
allow faster unblocking when a fault evolves from external to internal,
and hence a faster trip.
2.4.6 Permissive overreach schemes current reversal guard (Distance option only)
The re
commended setting is:
tREVERSAL GUARD = Maximum signaling channel reset time + 35 ms.
2.4.7 Blocking scheme current reversal guard (Distance option only)
The re
commended setting is:
Where Duplex signaling channels are used:
tREVERSAL GUARD = Maximum signaling channel operating time + 20 ms.
Where Simplex signaling channels are used:
tREVERSAL GUARD = Maximum signaling channel operating time - minimum signaling
channel reset time + 20 ms.
2.4.8 Aided DEF ground fault scheme - permissive overreach (Distance option only)
This PO
R scheme is similar to that used in all other ALSTOM Grid relays.
Send logic: IN> Forward pickup
Permissive trip logic: IN> Forward plus Channel Received
Note: The Time Delay for a permissive scheme aided trip would normally be
set to zero.
2.4.9 Aided DEF ground fault scheme - blocking (Distance option only)
This
scheme is similar to that used in all other ALSTOM Grid relays.
Send logic: DEF Reverse
Trip logic: IN> Forward, plus Channel NOT Received, with a small set delay
To allow time for a blocking signal to arrive, a short time delay on aided tripping must be
used. The recommended Time Delay setting = max. Signaling channel operating time +
20 ms.