EasyManua.ls Logo

Alstom MiCOM P54 Series - 8.4.9.1 Predictive OST setting

Alstom MiCOM P54 Series
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning P54x/EN CM/La4
MiCOM P543, P544, P545 & P546
CM) 10-51
CM
R
Z5
Z6
Z5'
Z6'
R5 R6R5'R6'
+jX
R
State 1
State 2
State 3
State 4
P1982ENa
Figure 6 Four state impedances
Depending on the Out of Step settings, follow one of the three options.
8.4.9.1 Predictive OST setting
Clea
r all alarms. Set Tost to zero. Based on healthy voltages (VA = VB = VC = 57.8V)
calculate the currents to generate the impedances as per Table 11.
State 1 State 2 State 3
Apply IA = IB = IC =
61.1
8.57
R
)56(
2
1
5
8.57
RRR
59.0
8.57
R
Angle
Duration 500 ms
Longer than 25 ms but
shorter that ‘Delta t’ set time
500 ms
Table 11: Predictive OST state sequence
Note: Angle in the table above is the angle between voltages and their
respective currents.
Now apply the 3 state sequence to the relay under test and observe that the relay has
tripped 3 phase and that an associated ‘Predictive OST’ alarm is displayed on the local LCD.
Clear all alarms.

Table of Contents