EasyManua.ls Logo

Alstom MiCOM P54 Series - 1.2.4 Event filtering

Alstom MiCOM P54 Series
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Measurements and Recording P54x/EN MR/La4
MiCOM P543, P544, P545 & P546
(MR) 8-7
MR
- Monday 27 October 2008 15:35:55 GMT A/R Lockout ON
MiCOM : MiCOM P54x
Model Number: P543218A1M054/50K
Address: 001 Column: 00 Row: 22
Event Type: Alarm event
- Tuesday 28 October 2008 20:18:22.988 GMT Zone 1 Trip ON
MiCOM : MiCOM P54x
Model Number: P543218A1M054/50K
Address: 001 Column: 0F Row: 30
Event Type: Setting event
As can be seen, the first line gives the description and time stamp for the event, whilst
the additional information that is displayed below may be collapsed via the +/– symbol.
For further information regarding events and their specific meaning, refer to Relay Menu
Database (P54x/EN MD). This is a standalone document not included in this manual.
1.2.4 Event filtering
It is possi
ble to disable the reporting of events from all interfaces that supports setting
changes. The settings that control the various types of events are in the record control
column. The effect of setting each to disabled is as follows:
Menu text Default setting Available settings
Clear Event No No or Yes
Selecting “Yes” will cause the existing event log to be cleared and an event will be
generated indicating that the events have been erased.
Clear Faults No No or Yes
Selecting “Yes” will cause the existing fault records to be erased from the relay.
Clear Maint. No No or Yes
Selecting “Yes” will cause the existing maintenance records to be erased from the relay.
Alarm Event Enabled Enabled or Disabled
Disabling this setting means that all the occurrences that produce an alarm will result in no
event being generated.
Relay O/P Event Enabled Enabled or Disabled
Disabling this setting means that no event will be generated for any change in logic input
state.
Opto Input Event Enabled Enabled or Disabled
Disabling this setting means that no event will be generated for any change in logic input
state.
General Event Enabled Enabled or Disabled
Disabling this setting means that no General Events will be generated.
Fault Rec. Event Enabled Enabled or Disabled
Disabling this setting means that no event will be generated for any fault that produces a
fault record.