P54x/EN PL/La4 Programmable Logic
(PL) 7-42
MiCOM P543, P544, P545 & P546
PL
DDB no. English text Source Description
1176 HMI Access Lvl 1
It indicates that level access 1 for HMI
interface is enabled
1177 HMI Access Lvl 2
It indicates that level access 2 for HMI
interface is enabled
1178 FPort AccessLvl1
It indicates that level access 1 for the front port
interface is enabled
1179 FPort AccessLvl2
It indicates that level access 2 for the front port
interface is enabled
1180 RPrt1 AccessLvl1
It indicates that level access 1 for the rear port
1 interface is enabled
1181 RPrt1 AccessLvl2
It indicates that level access 2 for the rear port
1 interface is enabled
1182 RPrt2 AccessLvl1
It indicates that level access 1 for the rear port
2 interface is enabled
1183 RPrt2 AccessLvl2
It indicates that level access 2 for the rear port
2 interface is enabled
1184 Monitor Bit 1 Commissioning Test
Monitor port signal 1 - allows mapped monitor
signals to be mapped to disturbance recorder
or contacts
1191 Monitor Bit 8 Commissioning Test Monitor port signal 8
1192 Hidden
1193 Not used
1194 PSL Int 1 PSL PSL internal node
1293 PSL Int 100 PSL PSL internal node
1294 VTS Ia> VT Supervision
“VTS I> Inhibit “ setting has been exceeded in
phase a
1295 VTS Ib> VT Supervision
“VTS I> Inhibit “ setting has been exceeded in
phase b
1296 VTS Ic> VT Supervision
“VTS I> Inhibit “ setting has been exceeded in
phase c
1297 VTS Va> VT Supervision Va has exceed 30 volts (drop off at 10 volts)
1298 VTS Vb> VT Supervision Vb has exceed 30 volts (drop off at 10 volts)
1299 VTS Vc> VT Supervision Vc has exceed 30 volts (drop off at 10 volts)
1300 VTS I2> VT Supervision “VTS I2> Inhibit “ setting has been exceeded
1301 VTS V2> VT Supervision V2 has exceed 10 volts
1302 VTS Ia delta> VT Supervision
Superimposed phase a current has exceed
0.1In
1303 VTS Ib delta> VT Supervision
Superimposed phase b current has exceed
0.1In
1304 VTS Ic delta> VT Supervision
Superimposed phase c current has exceed
0.1In
1305 to
1363
Not used
1364 CB1 Pre-Lockout Output from CB1 monitoring logic
1363 to
1374
Not used
1375 Teleprotection Disturbed
This is an output signal available in the PSL,
that could be mapped to “C Diff Failure” for
IEC870-5-103
1376 I>> Back Up Supervision
This applies only if distance primary FUN is
selected (in IEC870-5-103)
This signal is ON if an overcurrent stage is
selected to be enabled on VTS and distance is
blocked by VTS