Programmable Logic P54x/EN PL/La4
MiCOM P543, P544, P545 & P546
(PL) 7-49
PL
DDB no. English text Source Description
1495 CB1 CS2 AngHigh+
Line/Bus1 phase angle in range: +Angle 1-2 to
+180deg (anticlockwise from Vbus)
P544 and P546 only
1496 CB1 CS2 AngHigh-
Line/Bus1 phase angle in range: -Angle 1-2 to
-180deg (clockwise from Vbus)
P544 and P546 only
1497 Lead AR 1P PSL
If setting "Lead AR Mode" = Opto, then if input
DDB "LARSP" is high, the leader CB is
enabled for single phase autoreclose, if
"LARSP" is low, the leader CB is NOT enabled
for single phase autoreclose.
P544 and P546 only
1498 Lead AR 3P PSL
If setting "Lead AR Mode" = Opto, then if input
DDB "LAR3P" is high, the leader CB is
enabled for three phase autoreclose, if
"LAR3P" is low, the leader CB is NOT enabled
for three phase autoreclose.
P544 and P546 only
1499 CB2 Trip AR MemA
CB2 A Ph trip & AR initiation memory
P544 and P546 only
1500 CB2 Trip AR MemB
CB2 B Ph trip & AR initiation memory
P544 and P546 only
1501 CB2 Trip AR MemC
CB2 C Ph trip & AR initiation memory
P544 and P546 only
1502 to 1503 Not used
1504 Init APh AR Test PSL
DDB mapped in PSL from opto or comms
input. Input high-low operation will initiate APh
test trip & autoreclose cycle
P544 and P546 only
1505 Init BPh AR Test PSL
DDB mapped in PSL from opto or comms
input. Input high-low operation will initiate BPh
test trip & autoreclose cycle
P544 and P546 only
1506 Init CPh AR Test PSL
DDB mapped in PSL from opto or comms
input. Input high-low operation will initiate CPh
test trip & autoreclose cycle
P544 and P546 only
1507 Init 3P AR Test PSL
DDB mapped in PSL from opto or comms
input. Input high-low operation will initiate 3Ph
test trip & autoreclose cycle
P544 and P546 only
1508 Ext Fault APh PSL
DDB mapped in PSL from opto or comms
input: indicates external protection operated
for fault involving A phase
P544 and P546 only
1509 Ext Fault BPh PSL
DDB mapped in PSL from opto or comms
input: indicates external protection operated
for fault involving B phase
P544 and P546 only
1510 Ext Fault CPh PSL
DDB mapped in PSL from opto or comms
input: indicates external protection operated
for fault involving C phase
P544 and P546 only
1511 to 1516 Not used