EasyManua.ls Logo

Alstom MiCOM P54 Series - Page 625

Alstom MiCOM P54 Series
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Programmable Logic P54x/EN PL/La4
MiCOM P543, P544, P545 & P546
(PL) 7-91
DDB #886
Live Bus
&
&
&
1
DDB #889
Dead Line
DDB #887
Dead Bus
DDB #888
Live Line
DDB #881
CS1 Enabled
DDB #882
CS2 Enabled
DDB #885
SysSplit Enabled
This logic enables
Check Synchro to
function only for
Live Line / Live
Bus conditions.
DDB #883
Check Sync 1 OK
DDB #884
Check Sync 2 OK
DDB #880
SysChks Inactive
DDB #898
Ctl Check Sync
DDB #899
AR Sys Checks OK
Safety Interlock.
Logic must be
satisfied before any
manual CB closures
can proceed.
DDB #533
Force 3Pole Trip
DDB #858
AR Force 3 pole
PL

Table of Contents

Related product manuals