EasyManua.ls Logo

Alstom MiCOM P54 Series - Page 658

Alstom MiCOM P54 Series
1024 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
P54x/EN PL/La4 Programmable Logic
(PL) 7-124
MiCOM P543, P544, P545 & P546
DDB #744
Zone 1 N Start
DDB #748
Zone 2 N Start
DDB #752
Zone 3 N Start
DDB #760
Zone 4 N Start
DDB #777
IN>1 Start
DDB #778
IN>2 Start
DDB #779
IN>3 Start
DDB #780
IN>4 Start
1
DDB #1013
Phase Select N
DDB #522
Any Trip
&
DDB #036
Input L5
DDB #856
A/R Status 3P
DDB #857
A/R Status 1P
DDB #1013
Phase Select N
DDB #522
Any Trip
Pulse
10
0
&
&
1
DDB #959
Started Phase N
DDB #444
Reset Relays/LED
DDB #781
ISEF>1 Start
DDB #782
ISEF>2 Start
DDB #783
ISEF>3 Start
DDB #784
ISEF>4 Start
This reset
controls: Reset
latched relays,
Reset latched
LEDs, Reset A/R
Lockout.This logic clears all latched indications
at the start of Any Trip
This logic ensures correct N
indications for faults involving
ground. The pulse prevents pole
scatter affecting the N
indication.
Any Phase Start >>page8
DDB #756
Zone P N Start
>>page6 Any Phase Start
N Phase Start >> page8 then page 9 then page 10
Any Ground Start >> page8
PL

Table of Contents

Related product manuals