INSTALLATION INSTRUCTIONS
13.0 RS-485 COMMUNICATIONS, MODBUS RTU
13.1
The CD200 is compliant to the Modicon Modbus RTU standard.
Maximum number of registers that can be read at one time is limit-
ed to 32. Maximum number of booleans that can be read at one time
is limited to 256. All communications are 8 data bits, no parity, 1
stop bit. The baud rate is 9600. The MODBUS address list follows:
13.2
24 READ-ONLY STATUS BITS
READABLE IN MULTIPLES OF 8 BITS
STARTING AT 8-BIT BOUNDARIES
ADDRESS FUNCTION
10001 Syncing
10002 InSync1
10003 InSync2
10004 Purging
10005 Trying
10006 Firing
10007 LockOut
10008 FIRED
10009 Cranking
10010 Running
10011 Wrong Disk
10012 GLead Shutdown Grounded
10013 Remote Shutdown Present
10014 GLead Shutdown Logged
10015 Remote Shutdown Logged
10016 Overspeed Shutdown Logged
10017 WDOG1 Reset Latched
10018 WDOG2 Reset Event
10019 CheckSum Error
10020 LOW Supply Voltage
10021 No Charge
10022 Open Primary
10023 Shorted Primary
10024 Open Secondary