Sorensen DCS-E Series 3kW Supplies Installation
M362295-01 Rev D 2-13
R
ADIAL
D
ISTRIBUTION
M
ETHOD
With this method, power is connected to each load individually from a single pair of terminals
designated as the positive and negative distribution terminals. These terminals may be the
power supply output terminals, the terminals of one of the loads, or a distinct set of terminals
especially established for distribution use. Connecting the sense leads to these terminals will
compensate for losses and minimize the effect of one load upon another.
Figure 2-11 and Figure 2-12 show recommended load and sensing connections for multiple
loads. Local sense lines shown are default J3 connections. Refer to Section 3.3.1 Connecting
Remote Sense Lines for more information about grounding the sense line shield.
Figure 2-11 Multiple Loads with Local Sensing
Figure 2-12 Multiple Loads with Remote Sensing