10.2 Equipment Maintenance
WARNING!
The OCS has no user-serviceable parts.
All repairs must be carried out by Ampcontrol only.
If a fault develops, return the Cassette to Ampcontrol for repair. It is
essential that no attempt be made to repair the Cassette as any
attempt to dismantle or repair the Cassette can seriously compromise
the safety of the unit and voids product warranty.
It is recommended that the electrical protection system incorporating the OCS be subject to regular
functional tests at intervals determined by risk assessment or FMEA. These intervals typically coincide
with periodic maintenance checks and will cover (but not limited to) tests such as:
Earth Leakage injection tests
Earth Continuity tests
Earth Fault Lockout tests
Overcurrent injection tests
CAUTION!
When conducting insulation tests on the outgoing power circuits,
ensure that the Cable Connection Module (CCM) in the Protection
Element is disconnected. Failure to do so may damage the
Protection Element.
10.3 Disposal
ENVIRO
The electronic equipment discussed in this manual must not be
treated as general waste. By ensuring that this product is disposed of
correctly you will be helping to prevent potentially negative
consequences for the environment which could otherwise be caused by
incorrect waste handling of this product.