5.5. RESET
This option re-establishes the default settings of the instrument.
ANALYZER CONFIG:
Type of electrical equipment: Three Phase 4 wires
Frequency: not modified
Clamp full scale: not modified
Clamp type: not modified
Transforming ratio of voltmetric transformers: 1
Password: disabled
RECORDER CONFIG:
Start: manual (the recording is started
at 00 sec mark on clock after pressing
START/STOP)
Stop: manual
Integration period: 15min
Recording of harmonics: ON
Recording of voltage anomalies (sags and surges): ON
Voltage reference for detection of sags and surges: 110V
Upper limit for detection of sags and surges: 6%
Lower limit for detection of sags and surges: 10%
Selected voltages: V1, V2, V3
Selected voltage harmonics: THD, 01, 03, 05, 07
Selected currents: I1, I2, I3, IN
Selected current harmonics: THD, 01, 03, 05, 07
CO-GENERATION: OFF
Selected powers, Pf and cos: Pt, P1, P2, P3
Qti, Q1i, Q2i, Q3i
Qtc, Q1c, Q2c, Q3c
St, S1, S2, S3
Pft, Pf1, Pf2, Pf3
dpft, dpf1, dpf2, dpf3
Energies: Eat, Ea1, Ea2, Ea3
Erit, Eri1, Eri2, Eri3
Erct, Erc1, Erc2, Erc3
Est, Es1, Es2, Es3
The RESET command will not erase the instrument’s memory.