6
Replace Battery
Failure of a battery self-test causes the UPS to emit short beeps for one
minute and the replace battery LED illuminates. Refer to Trouble-
shooting in this manual.
Battery
Disconnected
The replace battery LED flashes and short beep is emitted every two
seconds to indicate the battery is disconnected.
Automatic Self-Test
The UPS performs a self-test automatically when turned on, and every
two weeks thereafter (by default).
During the self-test, the UPS briefly operates the connected equipment
on battery.
If the UPS fails the self-test, the replace battery LED
lights and
immediately returns to online operation. The connected equipment is
not affected by a failed test. Recharge the battery for 24 hours and per-
form another self-test. If it fails, the battery must be replaced.
Manual Self-Test
Press and hold the button for a few seconds to initiate the self-test.
On Battery Operation
The Smart-UPS switches to battery operation automatically if the utility power fails. While running
on battery, an alarm beeps four times every 30 seconds.
Press the
button (front panel) to silence the UPS alarm (for the current alarm only). If the utility
power does not return, the UPS continues to supply power to the connected equipment until the bat-
tery is exhausted.
If PowerChute
®
is not being used you must manually save your files and turn off the computer before
the UPS fully discharges the battery.
D
ETERMINING ON BATTERY RUN TIME
UPS battery life differs based on usage and environment. It is recommended that the battery/batteries
be changed once every three years. See the APC web site, www.apc.com
, for on battery run times.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC 100 and is the answer not in the manual?

APC 100 Specifications

General IconGeneral
ModelAPC 100
CategoryPower Supply
Output Power Capacity100VA/60W
Nominal Output Voltage230V
Nominal Input Voltage230V
Waveform TypeStepped approximation to a sinewave
Frequency50/60 Hz
Battery TypeLead-acid battery
Interface PortsUSB, Serial
Operating Temperature0°C to 40°C
Storage Temperature-15°C to 45°C
Humidity0% to 95% non-condensing
Audible Noise at 1mLess than 40 dB

Related product manuals