9.0 Specifications
Note: Where different, values for 208 Vac operation are given in brackets [ ].
9.1 Input
Nominal input voltage: single phase 240 Vac [208 Vac].
Nominal input frequency: 50 or 60 Hz.
On-line efficiency at full load: > 93% with fully charged batteries.
Input circuit breaker: 20 Amp (3000VA model), 30 Amp (5000VA model).
Input voltage selection: tap selected.
9.2 Transfer Characteristics
Frequency limits (on-line): 47 to 63 Hz.
Input voltage limits (on-line): 25 to +15% of the nominal input voltage.
Transfer to/from on-battery: 0 ms typical with computer loads, 1.5 ms maximum.
Transfer is synchronous with mains voltage phase.
Transfer to/from bypass: Transfers to and from bypass occur synchronously with
the utility voltage phase. Transfers both to and from bypass mode typically occur in 0
mS.
9.3 Output Characteristics
Maximum load: 3000 VA or 2250 W at 0.75 power factor (3000 VA model); 5000 VA
or 3750 W at 0.75 power factor [4700 VA or 3750 W at 0.8 power factor] (5000VA
model).
Nominal output voltage: 240 Vac; may be user set to 220, 225, or 230 Vac.
On-line voltage regulation: ±5%. User-selected Auto or Low sensitivity may
relax output voltage regulation to +5%, 12%.
On-line frequency regulation: Synchronized to the mains.
On-battery output voltage regulation: ±5%.
On-battery output frequency regulation: 50 or 60 Hz, ±0.1 Hz unless synchro-
nized to mains frequency during utility brownout.
On-battery output voltage total harmonic distortion: < 5%.
Protection: overcurrent & short circuit protected, latching shutdown on overload.
Output connections: (8) IEC 320 C13 business appliance receptacles.
9.4 Noise and surge isolation
Isolation: galvanic isolation, output neutral bonded to ground.
Normal mode EMI/RFI noise attenuation: 4060 dB over 100 kHz to 30 MHz.
Common mode EMI/RFI noise attenuation: 4060 dB over 100 kHz to 30 MHz.
Normal mode let-through: 0.7 % of applied ANSI C62.41 Cat. A or B ±6 kV test.
Common mode let-through: 1.0 % of applied ANSI C62.41 Cat. A or B ±6 kV test.