EPLACING BATTERY MODULES
X Y
Z [ \
] ^ _

Disconnecting the Battery for Transport
Always DISCONNECT THE BATTERY(s) before shipping in compliance with U.S.
Department of Transportation (DOT) and IATA regulations.
The battery(s) may remain in the UPS.
1. Shut down and disconnect any equipment attached to the UPS.
2. Shut down and disconnect the UPS from the power supply.
3. Unplug the battery connectors. Refer to Replacing Battery modules in this manual.
For shipping instructions contact APC at the Web site, www.apc.com
.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC RT and is the answer not in the manual?

APC RT Specifications

General IconGeneral
Nominal Output Voltage230V
TopologyDouble Conversion Online
Input Voltage Range160 - 286 V
Nominal Input Voltage230V
Transfer Time0 ms
Emergency Power Off (EPO)Yes
Output Frequency50/60 Hz +/- 3 Hz
Wave TypeSine wave
Battery TypeSealed Lead-Acid (SLA)
Interface PortsUSB
Audible AlarmAlarm when on battery
TypeUPS
Form FactorRack/Tower convertible
Dimensions432 x 482 x 89 mm (17 x 19 x 3.5 in)