TROUBLESHOOTING GUIDE
SYMPTOM TROUBLESHOOTING PROCEDURE / POSSIBLE REASON
Dehumidifier is not
draining properly.
Check drain trap to be sure it is clear.
Check drain line for continuous slope.
Confirm trap is properly installed and primed.
Dehumidifier is producing
hot air.
Reheat of outgoing air will cause a temperature increase across the dehumidifier,
which is normal.
Unit will possibly run continuously initially. After unit has “dried” home,
dehumidifier will cycle, reducing load.
HVAC fan does not turn
on when CYCLE TIME dial is
in “TEST” mode.
Make sure there is power to the HVAC equipment.
Check the wiring diagram for the R, C, W, Y, GH, and GS at the HVAC equipment,
thermostat, and the dehumidifier.
Make sure the sensor is connected to the Outdoor Temperature Sensor terminals
or the System Setup block is set to “TIMED” mode.
Check the voltage across the R and C terminals at the dehumidifier. Voltage
should be 18 VAC minimum–30 VAC maximum.
In “TEST” Mode, the HVAC fan will activate for 4 minutes, DO NOT LEAVE IN
TEST MODE AS DEHUMIDIFIER WILL NOT OPERATE.
Dehumidifier Blower is running,
but no airflow.
Normally Open Damper was used instead of Normally Closed Damper in backflow.
Damper needs to be switched.
Total HVAC system static is higher than 0.8” w.c.
Dehumidifier not adequately
dehumidifying.
Unit will need time to “dry” materials in home before effectively changing RH.
Too little airflow through dehumidifier.
Total HVAC system static is higher than 0.8” w.c.
Compressor is not turning on.
System undercharged.
LED CODES
Green LED
Activity Status
ON Solid Compressor ON
Blinking 1 second ON, 1 second OFF Sampling
Blinking 1/2 second ON, 1/2 second OFF Defrosting
Test Mode
At the end of test mode (3 minutes of DEH Fan + 1 minute of Compressor ON & DEH Fan), the Red and Green LEDs will turn ON and OFF alternately until
the knob has been turned away from “TEST”.
Red LED
Activity Status
1 Blink every 5 seconds The RH sensor is having problems
2 Blink every 5 seconds The temperature sensor is opened or shorted
3 Blink every 5 seconds The Model 70 fails to respond after 3 consecutive attempts
4 Blink every 5 seconds The refrigerant charge has been detected as low
5 Blink every 5 seconds The temperature sensor is out of the operating range
6 Blink every 5 seconds The frost sensor is opened or shorted
7 Blink every 5 seconds The float switch has opened