RECOV
Progressive recovery configuration COS: N/A
Permissions: Read/Write
Query
Command
Syntax: SN[#] RECOV?<CR>
Description: Requests the progressive recovery configuration setting.
Assignment
Command
Syntax: SN[#] RECOV=[value]<CR>
Description: Sets the progressive recovery configuration setting to [value].
Example: SN1 RECOV=ON<CR>
Response Syntax: SN[#] RECOV=[value]<CR>
Example: SN1 RECOV=ON<CR>
Node address 1 responds with a progressive recovery configuration setting of ON.
Parameters Range
value: auto mode deadband in degrees [OFF, ON]
Default: ON
This command is ignored if the controller type is set to humidistat.
HIBP
High balance point configuration COS: N/A
Permissions: Read/Write
Query
Command
Syntax: SN[#] HIBP?<CR>
Description: Requests the high balance point configuration setting.
Assignment
Command
Syntax: SN[#] HIBP=[value]<CR>
Description: Sets the high balance point configuration setting to [value] in degrees [scale].
Examples: SN1 HIBP=65<CR>
SN1 HIBP=4<CR>
SN1 HIBP=OFF<CR>
Response Syntax: SN[#] HIBP=[value][scale]<CR>
Example: SN1 HIBP=65F<CR>
Node address 1 responds with a high balance point configuration setting of 65°F.
Parameters Range
value: high balance point cut off temperature in 5°F or 3°C step [OFF]
Fahrenheit [40 – 85]
Celsius [3 – 30]
Default: 65F or 18C
scale: temperature scale [null, F, C]
The high balance point is dependent on the low balance point since the low balance point takes priority over the high balance point. If a HIBP
assignment command is received with a value that violates the 5°F (3°C) deadband between the high and low balance points, the command
is considered invalid and no response is sent. If the low balance point is modified, the high balance point is automatically increased if the
change to the low balance point violates the deadband. This command is only accepted if the thermostat is configured as heat pump and if
the outdoor temperature is available. Integer values must be within the range specified for the current temperature scale.
13