ALARM COMMANDS
FLTALMP
WPALMP
DEHALMP
SYSALMP
Air filter alarm period
Humidifier alarm period
Dehumidifier alarm period
HVAC system alarm period
COS: N/A
Permissions: Read/Write
Query
Command
Syntax: SN[#] [alarm]ALMP?<CR>
Description: Requests the [alarm] alarm period setting.
Assignment
Command
Syntax: SN[#] [alarm]ALMP=[value]<CR>
Description: Sets the [alarm] alarm period to [value].
Examples: SN1 FLTALMP=OFF<CR>
SN1 SYSALMP=12<CR>
Response Syntax: SN[#] [alarm]ALMP=[value]<CR>
Example: SN1 FLTALMP=OFF<CR>
Node address 1 responds with an air filter alarm period setting of OFF.
Parameters Range
alarm: alarm command code [FLT, WP, DEH, SYS]
value: alarm period setting in months
FLT [OFF, 1, 3, 6, 12]
WP, DEH, SYS [OFF, 1 – 12]
Default: OFF