EasyManua.ls Logo

Aprilaire 8800 - Page 35

Aprilaire 8800
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OH
Remote humidity COS: C3
Permissions: Read only
Query
Command
Syntax: SN[#] OH?<CR>
Description: Requests the remote humidity sensor reading.
Response or
COS Message
Syntax: SN[#] OH=[value]%<CR>
Example: SN1 OH=25%<CR>
Node address 1 responds with a remote humidity of 25% RH.
Parameters Range
value: humidity sensor value [--, 0 – 99]
The remote humidity reading source is from Support Module 1, Sensor 2 configured as monitor. If a query command is received and Support
Module 1 is not connected or is temperature only, it responds with SN[n] OH=--%<CR>.
If the value of the remote humidity changes by 1% RH or more, a C3 COS unsolicited message is issued (if C3 is ON).
BIHUM
Built-in humidity COS: N/A
Permissions: Read only
Query
Command
Syntax: SN[#] BIHUM?<CR>
Description: Requests the built-in humidity sensor reading.
Response Syntax: SN[#] BIHUM=[value]%<CR>
Example: SN1 BIHUM=30%<CR>
Node address 1 responds with a built-in humidity of 30% RH.
Parameters Range
value: built-in humidity sensor value [--, 0 – 99]
If the humidity sensor has an error, the response is SN[n] BIHUM=--%<CR>.
RTS
Node remote temperature sensor COS: N/A
Permissions: Read only
Query
Command
Syntax: SN[#] RTS?<CR>
Description: Requests the node’s direct-wired remote temperature sensor (T1 and T2 terminals) reading.
Response Syntax: SN[#] RTS=[value][scale]<CR>
Example: SN1 RTS=68F<CR>
Node address 1 responds with a remote temperature reading of 68°F.
Parameters Range
value: remote temperature sensor value
Fahrenheit [32 – 99]
Celsius [0 – 40]
no sensor attached or error [--]
scale: temperature scale [F, C]
F: Fahrenheit
C: Celsius
If the remote temperature sensor is not attached or has an error, the response is SN[n] RTS=--[scale]<CR>.
35