3
WARRANTY
Aqualisa products are supplied complete with a 1 year guarantee that can
be upgraded by registering this product with Aqualisa.
For details see: www.aqualisa.co.uk/warranty
BEFORE YOU START
This shower should be installed by a competent person in compliance with
current Water Supply Regulations. For further details contact your Local
Water Authority.
a. Identify all components and check pack contents.
b. Turn o water supplies.
c. Suitable full bore isolation valves must be fitted to both supplies in
accordance with current Water Supply Regulations and our terms of
warranty. Valves must be accessible for warranty and servicing.
Before making any pipe connections all supplies MUST be
thoroughly flushed to remove any debris.
WATER SUPPLY REQUIREMENTS
Hot Water Maximum: 65˚C Cold Water Minimum: 5˚C
Recommended 60-65˚C Recommended 10-15˚C
Always maintain a 10˚C dierence between hot system temperature and
maximum hot setting of valve.
Operating Pressure Range: Min. 0.15 bar, Max. 5.0 bar
When water pressure is higher than 5 bar a pressure reducing valve (not
supplied) must be fitted before the mixer. A setting of 3 bar is recommended.
This valve is suitable for gravity stored, gravity boosted (pumped),
balanced high pressure and combination boiler systems.
For gravity and gravity pumped systems use 22mm supply pipes and
reduce to 15mm for connection to the shower valve.