5
5 - 8
List of Item Codes
Item code Parameter
01 Control system schedule
02 Control system schedule
03 Control system schedule
04 Snowfall sensor operation 0 = No sensor, control performed
1 = No sensor, control not performed
2 = Sensor present, control performed
3 = Sensor present, control not performed
05 Outdoor fan quiet mode 0 = Disabled 1 = Quiet mode
06 Defrost fan speed selection 0 = Disabled 1 = LL fan speed
(This function is not present with the DC-INV.)
07 Ignore capacity 0 = Disabled 1 = Ignores capacity ratio
08 Control system schedule
09 Control system schedule
0A Control system schedule
0b Control system schedule
0C Forced operation of 0 = Disabled
indoor unit drain pump 1 = During cooling only, 2 hours stopped + 20 minutes operating
(regardless of whether the unit is running or stopped)
2 = During cooling only, 4 hours stopped + 20 minutes operating
(regardless of whether the unit is running or stopped)
3 = At all times, 4 hours stopped + 20 minutes operating
4 = At all times, 2 hours stopped + 20 minutes operating
0d Odor countermeasure when 0 = Disabled 1 = Odor countermeasure is active
indoor cooling thermostat is OFF
0E Cool only 0 = Heat pump 1 = Cool only
0F Control system schedule
10 Control system schedule
11 Multi-floor installation 0 = No 1 = Yes
12 Control system schedule
13 Control system schedule
50 Demand 1 40%, 45% ... 100% ... 160%
51 Demand 2 40%, 45% ... 100% ... 160%
52 Current control level 40%, 45% ... 100% ... 160%, –1 (no control)
* Figures in parentheses indicate the data at the time of shipment from the factory.