1-3. Other Component Specifications
Outdoor Units AES71PIH
MODEL No. Outdoor Unit
Power Transformer
Rated
Primary VAC, Hz
Secondary
Coil resistance Ω WHT – WHT : 300
BRN – BRN : 2.2
Thermal cut off temperature °C
Thermistor (Coil sensor) : TH7
Resistance KΩ –10°C : 23.7 ± 5 % , 20°C : 6.5 ± 5 %
– 5°C : 18.8 ± 5 % , 30°C : 4.4 ± 5 %
0°C : 15.0 ± 5 % , 40°C : 3.1 ± 5 %
5°C : 12.1 ± 5 % , 45°C : 2.6 ± 5 %
10°C : 9.7 ± 5 % , 50°C : 2.1 ± 5 %
Thermistor (Discharge gas sensor) : TH
8
Resistance KΩ 60°C : 13.8 , 90°C : 5.1
70°C : 9.7 , 100°C : 3.8
75°C : 8.2 , 110°C : 2.8
80°C : 7.0 , 120°C : 2.2
85°C : 5.9 , 130°C : 1.7
Relay (Comp. Magnetic Contactor)
Coil rated VAC
Contact rating VAC, A
Coil resistance (at 25°C) Ω
Solenoid coil or 4 way valve
4 way valve
Solenoid coil
AES71PIH
–
–
230 V, 50 Hz
14 V, 0.4A
–
PBC - 41E - S4
PTC - 51H - S1
–
–
–
–
–
STF-01AJ512D1