1 - 62
1-5. Refrigerant Flow Diagram
Outdoor Unit: AES125PIC-PIH Indoor Unit: 125 Type
1-6. Operating Range
M
EC
P
Cooling cycle
Heating cycle
Distributor
Distributor
Strainer
Strainer
Modulator
Liquid line
service valve
Electronic ref.
control valve
Freeze-prevention coil
(Attached to the heat exchanger)
Accumlator
Compressor
Heat
exchanger
Heat
exchanger
φ15.88
φ9.52
Muffler
4-way valve
Gas line
service valve
Temperature Indoor air intake temp.
Outdoor air intake temp.
Cooling
Heating
Maximum
Maximum
Minimum
32°C DB / 23°C WB 43°C DB
18°C DB / 14°C WB
–15°C DB
30°C DB / – WB
15°C WB
–15°C WB
04-309 Sanyo-1_p96-127 10/27/04 2:07 PM Page 107