1-2. Major Component Specifications
(B) Outdoor Units
AES125PIH
MODEL No.
Source
Controller P.C.B. Ass’y
Control circuit fuse
Compressor
Model…..number
Source
Nominal output W
Compressor oil cc
Coil resistance
C – R : 0.169 R – S : 0.169
(Ambient temperature 25°C) C – S : 0.169
Safety control
Overload relay models
Operating temperature Open °C
Close °C
Crank case heater
Refrigerant amount at shipment kg
High pressure switch
Fan
Number…diameter mm
Air circulation (Hi)
m
3
/h
Fan speeds (Max.)
Fan motor
Model No.
Source
No. of pole
Nominal output W
Coil resistance RED – WHT : 30.5 WHT – BLU : 30.5
(Ambient temperature 20°C) BLU – RED : 30.5
Safety device
Operating temperature Open °C
Close °C
Run capacitor VAC, µF
Heat exchange
Coil
Rows…..fin pitch mm
Face area
m
2
AES125PIH
250 V, 25 A
Discharge temperature control
2,700
126 V (DC) / 3 phase / 60 Hz (Inverter drive)
C-9RVN273H0W
220 - 230 - 240 V / 1 phase / 50/60 Hz
CR-CR254GVH56 (Microprocessor)
R410A - 3.6
Set pressure OFF
kg/cm
2
1,900
6,000
ON
kg/cm
2
~800 rpm (Inverter drive control)
2…..ø460
Propeller
DAJ12-95A61A,B
8
~280 V / 3 phase
90
Aluminium plate fin / Copper tube
2…..2.0
1.080
04-163 Sanyo-1_p62-95 7/9/04 8:09 PM Page 82

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Argo AWS36PH and is the answer not in the manual?

Argo AWS36PH Specifications

General IconGeneral
BrandArgo
ModelAWS36PH
CategoryAir Conditioner
LanguageEnglish

Related product manuals