2 - 4
Defrost control
(1) Frost detection
1. Outdoor heat exchanger temperature (C1) method
(15-minute mask after operation start)
2. Outdoor air temperature is –13°C or above and outdoor heat
exchanger temperature (C1) of –18°C or below is detected continu-
ously for 20 seconds.
3. Outdoor air temperature is below –13°C and outdoor heat exchang-
er temperature (C1) of below (outdoor air temperature – 5)°C is
detected continuously for 20 seconds.
(2) Defrost cancel
• Defrost end conditions
1. Outdoor heat exchanger temperature (C1) rises to 12°C or higher.
2. Outdoor heat exchanger temperature is 7°C or higher continuously
for 1 minute.
3. Defrost time of 10 minutes has elapsed.
(3) Startup operation
After defrost ends, the compressors and outdoor unit fan stop for approxi-
mately 40 seconds, then operation begins in heating mode.
continuously for 3 minutes or for 60 minutes in total.