14.3. Set up of maximum allowable refrigerant weight in cylinder)
It is recommended that the recovery cylinders are filled to 80% of their capacity. Maximum
cylinder weigh set up function allows automatic protection to prevent the storage cylinder from
being overfilled.
- Press and hold depressed the "START"
button and switch ON the unit (on the main
power switch at back).
The display will indicate CYL.
- By pressing “UP” or “DOWN” button, set the
maximum weight to be 80% of the cylinder
capacity.
For the 12kg cylinder set maximum 10kg.
For 25kg cylinder set max. 20kg.
For 27kg cylinder, set max 22kg…
- When display indicate the selected amount
press “START” button to confirm the
maximum cylinder set up.