28
Armstrong International
221 Armstrong Blvd., Three Rivers, Michigan, 49093 - USA
Ph. (269) 279-3602 Toll Free (888) 468-4673 Fax (269) 279-3130
Important!
The Error Temp value cannot be set lower than the Max value plus the Above Setpoint value.
Example 2
Note! Adjusted Setpoint value does not need to be the same as the Default value. Both Adjusted Setpoint and
Default can be set within the Max and Min range only.
M
I
X
E
D
T
E
M
P
E
R
A
T
U
R
E
F
L
U
C
T
U
A
T
I
O
N
Max.
Hot
Cold
ALERT
ALERT
SHUT DOWN TO
FULL COLD
115°F
(5°F Above Setpoint)
105°F (5°F Below Setpoint)
100°F
120°F
158°F Error Temp.
Min.
Setpoint
110°F Setpoint