Commissioning
Commissioning must be carried out in accordance with these instructions by designated, qualied and competent
personnel.
4mm HEX
Secure the Y-Strap bracket at the bottom of
the valve using the battery holder screws &
the supplied screw .
Ensure that the system is powered and
the display on the Electronics Module is
illuminated.
Make sure the hot and cold inlet supplies are at
their designated pressures and temperatures.
Close all the mixed water outlets and turn on
the circulating pump.
Ensure the system is powered o and the 4 pin plug is unplugged on the electronics module.
Flood the system in the following sequence:
• Open the cold water supply isolation valve(s).
• Open the outlet ow isolation valve(s).
• Open the hot water supply isolation valve(s).
• Once ooded, connect and secure the 4 pin plug to the electronics module.
Close and secure the Electronics Module with the 2 x 4mm hexagon socket screws provided.
Note! The Electronics Module must be closed for the DRV80 to function.