Commissioning
Commissioning must be carried out in accordance with these instructions by designated, qualied and competent
personnel.
4mm HEX
Secure the Y-Strap bracket at the bottom of
the valve using the battery holder screws &
the supplied screw .
Ensure that the system is powered and
the display on the Electronics Module is
illuminated.
Make sure the hot and cold inlet supplies are at
their designated pressures and temperatures.
Close all the mixed water outlets and turn on
the circulating pump.
Ensure the system is powered o󰀨 and the 4 pin plug is unplugged on the electronics module.
Flood the system in the following sequence:
Open the cold water supply isolation valve(s).
Open the outlet ow isolation valve(s).
Open the hot water supply isolation valve(s).
Once ooded, connect and secure the 4 pin plug to the electronics module.
Close and secure the Electronics Module with the 2 x 4mm hexagon socket screws provided.
Note! The Electronics Module must be closed for the DRV80 to function.
1
2
3
4
5
6
7

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Armstrong The Brain DRV80 and is the answer not in the manual?

Armstrong The Brain DRV80 Specifications

General IconGeneral
BrandArmstrong
ModelThe Brain DRV80
CategoryControl Unit
LanguageEnglish

Related product manuals