1
Click Enable Disinfection checkbox and set the Disinfection Timeout value.
Disinfection Timeout is the number of minutes the temperature alert and error displays are disabled to allow
for disinfection and cool down of the blend circuit before switching back on automatically, i.e. if Disinfection
Timeout is set to 30 minutes then the DRV80 has that time to complete the disinfection and cool down before
entering an error condition and switching to full cold.
Please note the following:
Disinfection Timeout starts when Trigger is pressed.
During the Disinfection Timeout the disinfection and cool down must be completed manually and the
DRV80 returned to Setpoint (normal operation within the setpoint limits).
The Disinfection Timeout can be set up to a
maximum of 1800 minutes (30 hours).
Disinfection Status
This shows the status of the disinfection cycle.
Disinfection Control
The controls for the Disinfection Cycle.
Disinfection Setup
The controls that enable a Disinfection Cycle to be run and sets the Disinfection Timeout feature.
Disinfection Setpoint
The temperature at which the thermal disinfection will be completed (must not exceed 185 °F / 85 °C).
Disinfection Setup
Max.
Hot
Cold
ALERT
ALERT
SHUT DOWN TO
FULL COLD
Above Setpoint
Below Setpoint
Min.
Setpoint
Setpoint Default
M
I
X
E
D
T
E
M
P
E
R
A
T
U
R
E
F
L
U
C
T
U
A
T
I
O
N
NORMAL
OPERATION