dump valve
position
Return to Hot
Water Supply Inlet
Problem: “Blend circuit does not fully return to normal within the Disinfection Timeout
period...”
Blend circuit / Control software
Check the following:
• Disinfection Timeout value.
• Cool Down start and nish times.
• Early abort of disinfection cycle.
• Use of a dump valve to speed up cool
down time.