68
Armstrong International
221 Armstrong Blvd., Three Rivers, Michigan, 49093 - USA
Ph. (269) 279-3602 Toll Free (888) 468-4673 Fax (269) 279-3130
Problem: “Water leaking from DRV80...”
Check all DRV seals
Check all internal seals for wear and / or
damage. Clean and ret seals. If problem
persists, replace seals. Only use silicone
based lubricants on rubber seals in cartridge
(see page 50).
Check drain plug
Check drain plug and seal for wear and / or
damage. Make sure drain plug and seal are
tted and tightened adequately. If problem
persists, replace both plug and seal.
Check inlet and outlet connections
Check inlet and outlet thread joints. Check a
correct seal has been made with PTFE thread
sealing tape or liquid sealant. Oil-based, non-
setting joint compounds should not be used.
DRV body failure
DRV80 replacement required.