EasyManua.ls Logo

Artesyn ATCA-7480 - Table 2-1 Environmental Requirements

Default Icon
330 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Hardware Preparation and Installation
ATCA-7480 Installation and Use (6806800T17A)
45
Table 2-1 Environmental Requirements
Requirement Operating Non-Operating
Temperature Normal Operation: +5 °C (41 °F) to +40
°C (104 °F) according to Telcordia GR-
63-CORE (NEBS) and ETSI EN 300 019-
1-3, Class 3.1
Exceptional Operation: -5 °C (23 °F) to
+55 °C (131 °F) according to Telcordia
GR-63-CORE (NEBS)
Note: This exceeds ETSI EN 300 019-1-
3, Class 3.1E requirements (-5°C to
+45°C)
-40 °C (-40 °F) to +70 °C (158 °F) according
to Telcordia GR-63-CORE (NEBS) and ETSI
EN 300 019-1-2, Class 2.3
Note: This exceeds ETSI EN 300 019-1-1,
Class 1.2 requirements (storage from -
25 °C (-13 °F) to +55 °C (131 °F)
Note: This may be further limited by
installed accessories.
Temp. Change +/- 0.25 °C/min according to Telcordia
GR-63-CORE
+/- 0.25 °C/min
Rel. Humidity Normal Operation: 5%rH to 85%rh non-
condensing
Exceptional Operation: 5%rH to 90%rh
non-condensing
According to Telcordia GR-63-CORE
(NEBS) and EN 300 019-1-3, Classes 3.1
and 3.1E
5% to 95% non-condensing according to
Telcordia GR-63-CORE (NEBS) and EN 300
019-1-1, Classes 1.2 and 2.3
Vibration 1g from 5 to 200Hz and back to 5Hz at
a rate of 0.25 octave/minute
(according to Telcordia GR-63-core)
5-20 Hz at 0.01 g
2
/Hz (according to
Telcordia GR-63-core and ETSI EN 300
019-2-2)
20-200 Hz at -3 dB/octave Hz (according
to Telcordia GR-63-core and ETSI EN 300
019-2-2)
Random 5-20Hz at 1 m
2
/s
3
Random 20-200Hz at 3 m
2
/s
3
Shock Half-sine, 11 ms, 30 m/s
2
Blade level packaging
Half-sine, 6 ms at 180 m/s
2
Free Fall - 1.2 m/ packaged (according to ETSI 300
019-2-2)
100 mm unpackaged (according to
Telcordia GR-63-core)

Table of Contents