SWIMMING POOL HEAT PUMP User and service manual
POMPE À CHALEUR POUR PISCINE Manuel d’installation et d’utilisation
ZWEMBAD WARMTEPOMP Gebruiker en service manual
BOMBA DE CALOR PARA PISCINA Manual del usuario y de servicio
SCHWIMMBAD - WÄRMEPUMPE Benutzer - und Wartungshandbuch
PISCINA POMPA DI CALORE Istruzioni per l'uso e di servizio
BOMBA DE CALOR DE PISCINA Manual do usuário e serviço
PRO ELYO INVERBOOST NN
EN
FR
NL
IT
ES
DE
PT

Questions and Answers

  • B
    benjaminkeySep 1, 2025
    What does 'low ambient temperature protection' mean for my Astralpool PROELYXP14i Heat Pump?
    • N
      Natalie GarciaSep 1, 2025
      The 'low ambient temperature protection' message on your Astralpool Heat Pump indicates that the unit is either being used outside of its intended environment or that there is a sensor abnormality. Stop using the unit if it is beyond its operating scope, or change the sensor.
  • M
    Michelle MedinaSep 12, 2025
    What to do if my Astralpool Heat Pump has a gas return sensor failure?
    • R
      Rebecca RossSep 13, 2025
      If your Astralpool Heat Pump shows a gas return sensor failure, it could be due to the sensor being in an open or short circuit, or the wiring of the sensor being loose. Check or change the sensor and re-fix the wiring of the sensors.
  • M
    melindahuntAug 31, 2025
    How to resolve communication failure between Main control board and Driving board in Astralpool Heat Pump?
    • D
      Daniel Gomez PhDAug 31, 2025
      A communication failure between the Main control board and Driving board in your Astralpool Heat Pump is likely caused by a poor connection of the communication wire or a damaged wire. Check the wire connection and replace the wire if necessary.
  • M
    Matthew GonzalezSep 15, 2025
    What should I do if my Astralpool PROELYXP14i Heat Pump shows an input power failure?
    • D
      daniellerobertsonSep 15, 2025
      If your Astralpool Heat Pump indicates an input power failure, it's likely due to supply voltage fluctuations. Check whether the voltage is stable.
  • S
    Stephanie GutierrezSep 14, 2025
    What to do if my Astralpool Heat Pump has an exhaust piping sensor failure T6?
    • E
      eroblesSep 14, 2025
      If your Astralpool Heat Pump shows an exhaust piping sensor failure T6, it could be due to the sensor being in an open or short circuit, or the wiring of the sensor being loose. Check or change the sensor and re-fix the wiring of the sensors.
  • S
    Samantha MartinezSep 23, 2025
    What does compressor phase failure mean for my Astralpool Heat Pump?
    • M
      Marc DunnSep 23, 2025
      Compressor phase failure in your Astralpool Heat Pump means that the compressors U, V, W are connected to one phase or two phases. Check the actual wiring according to the circuit diagram.
  • Q
    qhobbsAug 27, 2025
    How to fix communication failure between controller and main board in Astralpool Heat Pump?
    • J
      josephwhitakerAug 28, 2025
      A communication failure between the controller and main board of your Astralpool Heat Pump is often due to a poor signal wire connection, a damaged signal wire, or a controller malfunction. Check and reconnect the signal wire, replace the signal wire, turn off the electricity supply and restart the machine, or replace the controller.
  • R
    Rhonda SmithAug 27, 2025
    What to do if my Astralpool Heat Pump displays a low pressure failure TS5?
    • M
      Miss Melissa CooperAug 27, 2025
      If your Astralpool Heat Pump is showing a low pressure failure TS5, it could be caused by a blocked EEV or jammed pipe system, abnormal motor speed or motor damage, or gas leakage. You should check the EEV and piping system, check the motor, use a high-pressure gauge to check the pressure value and check the refrigeration system.
  • V
    vhoganAug 26, 2025
    What causes T6 exhaust too high protection in Astralpool Heat Pump?
    • K
      Kerri JohnsonAug 26, 2025
      T6 exhaust too high protection in your Astralpool Heat Pump can result from a lack of gas, low water flow, a blocked piping system, or a faulty exhaust temperature sensor. Address this by checking the high-pressure gauge and filling with gas if needed, inspecting the waterway system and filtration pump, checking the piping system for blockages, and replacing the exhaust temperature sensor.
  • K
    Kayla ButlerAug 25, 2025
    Why is my Astralpool PROELYXP14i Heat Pump showing compressor current protection?
    • M
      Michelle MichaelAug 26, 2025
      Compressor current protection in your Astralpool Heat Pump can occur due to several reasons: the compressor current being too large instantaneously, incorrect connection for compressor phase sequence, compressor accumulations of liquid and oil, a damaged compressor or driver board, abnormal water flow, or power fluctuations. To resolve this, check the compressor, compressor phase, power range, phase sequence connection, the waterway system and filtration pump, and mains power input.

Summary

Specifications

Location and Connection

5.1 Heat Pump Location

Details optimal placement requirements and considerations for the heat pump unit.

5.4 Initial Operation

Outlines the procedure for starting the heat pump for the first time.

Electrical Wiring

Wiring Diagrams

Visual schematics showing electrical connections for various heat pump models.

6.6 Electrical Connection

Provides guidelines and specifications for connecting the heat pump to the power supply.

Start-up of the Heat Pump

7.2.12 Auto Mode

Describes the unit's auto mode, including heating, cooling, and switching logic.

7.3 Heating Operation Logic

Details the operational logic and parameters for heating modes.

7.4 Cooling Operation Logic

Details the operational logic and parameters for cooling modes.

Troubleshooting

8.1 Error Code Display on LED Wire Controller

Lists error codes, their causes, and recommended solutions.

8.2 Other Malfunctions and Solutions (No display on LED wire controller)

Addresses issues not indicated by error codes and their resolutions.

Exploded Diagram

Astralpool PROELYXP14i Specifications

General IconGeneral
ModelPROELYXP14i
Heating Capacity14 kW
Power Supply230V / 1ph / 50Hz
Power Consumption2.8 kW
COP5.0
RefrigerantR32
Noise Level52 dB(A)
Compressor TypeRotary
Heat ExchangerTitanium
Max Water Temperature40°C
Water Flow Rate4.0 m³/h
Operating Temperature Range-10°C to +43°C