SWIMMING POOL HEAT PUMP User and service manual
POMPE À CHALEUR POUR PISCINE Manuel d’installation et d’utilisation
ZWEMBAD WARMTEPOMP Gebruiker en service manual
BOMBA DE CALOR PARA PISCINA Manual del usuario y de servicio
SCHWIMMBAD - WÄRMEPUMPE Benutzer - und Wartungshandbuch
PISCINA POMPA DI CALORE Istruzioni per l'uso e di servizio
BOMBA DE CALOR DE PISCINA Manual do usuário e serviço
PRO ELYO INVERBOOST NN
EN
FR
NL
IT
ES
DE
PT

Questions and Answers

  • P
    phillipsrobertSep 1, 2025
    What does 'low ambient temperature protection' mean for my Astralpool PROELYXP16i?
    • W
      William HowellSep 1, 2025
      The 'low ambient temperature protection' message on your Astralpool Heat Pump indicates that the unit is either being used outside of its intended environment or that there is a sensor abnormality. Stop using the unit if it is beyond its operating scope, or change the sensor.
  • D
    danielosborneSep 12, 2025
    What to do if my Astralpool Heat Pump has a gas return sensor failure?
    • R
      Rebecca AndradeSep 13, 2025
      If your Astralpool Heat Pump shows a gas return sensor failure, it could be due to the sensor being in an open or short circuit, or the wiring of the sensor being loose. Check or change the sensor and re-fix the wiring of the sensors.
  • D
    Danielle BryanAug 30, 2025
    How to resolve communication failure between Main control board and Driving board in Astralpool PROELYXP16i?
    • S
      Steven RhodesAug 31, 2025
      A communication failure between the Main control board and Driving board in your Astralpool Heat Pump is likely caused by a poor connection of the communication wire or a damaged wire. Check the wire connection and replace the wire if necessary.
  • E
    ericsantosSep 15, 2025
    What should I do if my Astralpool PROELYXP16i shows an input power failure?
    • C
      Craig WhiteheadSep 15, 2025
      If your Astralpool Heat Pump indicates an input power failure, it's likely due to supply voltage fluctuations. Check whether the voltage is stable.
  • A
    Amy SaundersSep 14, 2025
    What to do if my Astralpool PROELYXP16i has an exhaust piping sensor failure T6?
    • M
      Michael RomeroSep 14, 2025
      If your Astralpool Heat Pump shows an exhaust piping sensor failure T6, it could be due to the sensor being in an open or short circuit, or the wiring of the sensor being loose. Check or change the sensor and re-fix the wiring of the sensors.
  • B
    brianyoungSep 22, 2025
    What does compressor phase failure mean for my Astralpool PROELYXP16i Heat Pump?
    • R
      Richard RoseSep 22, 2025
      Compressor phase failure in your Astralpool Heat Pump means that the compressors U, V, W are connected to one phase or two phases. Check the actual wiring according to the circuit diagram.
  • B
    Brian GloverAug 27, 2025
    How to fix communication failure between controller and main board in Astralpool PROELYXP16i Heat Pump?
    • J
      James FlemingAug 27, 2025
      A communication failure between the controller and main board of your Astralpool Heat Pump is often due to a poor signal wire connection, a damaged signal wire, or a controller malfunction. Check and reconnect the signal wire, replace the signal wire, turn off the electricity supply and restart the machine, or replace the controller.
  • N
    Nicole FoxAug 27, 2025
    What to do if my Astralpool PROELYXP16i Heat Pump displays a low pressure failure TS5?
    • S
      Stephen DeanAug 27, 2025
      If your Astralpool Heat Pump is showing a low pressure failure TS5, it could be caused by a blocked EEV or jammed pipe system, abnormal motor speed or motor damage, or gas leakage. You should check the EEV and piping system, check the motor, use a high-pressure gauge to check the pressure value and check the refrigeration system.
  • J
    Jacob MeyersAug 26, 2025
    What causes T6 exhaust too high protection in Astralpool Heat Pump?
    • G
      garciamatthewAug 27, 2025
      T6 exhaust too high protection in your Astralpool Heat Pump can result from a lack of gas, low water flow, a blocked piping system, or a faulty exhaust temperature sensor. Address this by checking the high-pressure gauge and filling with gas if needed, inspecting the waterway system and filtration pump, checking the piping system for blockages, and replacing the exhaust temperature sensor.
  • D
    Dr. Michael EstradaAug 25, 2025
    Why is my Astralpool Heat Pump showing compressor current protection?
    • K
      Kathryn RichardsAug 26, 2025
      Compressor current protection in your Astralpool Heat Pump can occur due to several reasons: the compressor current being too large instantaneously, incorrect connection for compressor phase sequence, compressor accumulations of liquid and oil, a damaged compressor or driver board, abnormal water flow, or power fluctuations. To resolve this, check the compressor, compressor phase, power range, phase sequence connection, the waterway system and filtration pump, and mains power input.

Summary

Description

1.1 Included with your Heat Pump

Lists all included accessories with the heat pump.

Specifications

Technical Data Overview

Comprehensive technical specifications for the PRO ELYO INVERBOOST NN series.

Location and Connection

5.1 Heat Pump Location

Guidelines for choosing an optimal installation site for the heat pump.

5.4 Initial Operation

Procedure for starting and operating the heat pump for the first time.

Electrical Wiring

6.1 Inverter Swimming Pool Heat Pump Wiring Diagram

Wiring diagram for models 71676/71677/71678/71679/71680.

6.3 Inverter Swimming Pool Heat Pump Wiring Diagram

Wiring diagram for models 71682/71683.

6.4 Inverter Swimming Pool Heat Pump Wiring Diagram

Wiring diagram for model 68822 (R410A).

6.5 Inverter Swimming Pool Heat Pump Wiring Diagram

Wiring diagram for models 68821/68823 (R410A).

6.6 Electrical Connection

Requirements and guidelines for safe and proper electrical hookup.

Start-up of the Heat Pump

7.3 Heating Operation Logic

Logic and conditions governing the heat pump's heating cycles.

7.4 Cooling Operation Logic

Logic and conditions governing the heat pump's cooling cycles.

Troubleshooting

8.1 Error Code Display

Guide to interpreting error codes shown on the LED controller.

8.2 Other Malfunctions and Solutions

Troubleshooting for issues not indicated by error codes.