Real time measurements: (@: 10h 1Fh)
Address (bytes)
Description
10h 13h
Pressure current value
Example: reading of 524000 (7FEE0h) = 524 x 1000, thus the real value is 524.
14h 17h
Pressure unit code
Example: reading 6000 (1770h) = 6 x 1000, thus the value is 6 which corresponds to
Pa (see Unit table).
18h 1Bh
Flow current value
Examples: reading 20000 (4E20h) = 20 x 1000, thus the real value is 20
reading - 108 (FFFFFF94h) = - 0.108 x 1000, thus the real value is - 0.108
(see Basic notions)
1Ch 1Fh
Flow unit code
Example: reading 8000 (1F40h) = 8 x 1000 thus the value is 8, which
corresponds to the Pa/s unity.
Exchange zone: (@: 20h 9Fh)
Address (bytes)
Description
20h 9Fh
Cycle results exchange zone.
Parameters reading and writing exchange zone.