Line Function
Setting range
or display
Setting
increment
Basic
setting
Holidays, heating circuit 1
641 Preselection Period 1 to 8 Period 1
642 Start (Day / Month) 01.01... 31.12 1
643 End (Day / Month) 01.01... 31.12 1
648 Operating level (during the holidays) Frost protection, Reduced Frost
protection
Holidays, heating circuit 2
If the installation consists of 2 heating circuits (Only with the 2
nd
circuit kit option).
651 Preselection Period 1 to 8 Period 1
652 Start (Day / Month) 01.01... 31.12 1
653 End (Day / Month) 01.01... 31.12 1
658 Operating level (during the holidays) Frost protection, Reduced Frost
protection
Heating Circuit 1
710 Comfort heating setpoint from reduced setpoint to 35°C 0,5 °C 20 °C
712 Reduced setpoint from frost protection setpoint…
to comfort setpoint
0,5 °C 18 °C
714 Frost protection setpoint from 4°C…
to reduced setpoint
0,5 °C 8 °C
Cooling circuit 1
901 Operating mode Off, Automatic Off
902 Comfort cooling setpoint 17... 40 °C 0,5 °C 24 °C
907 Release 24h/day, Time program HC,
Time program 5 / Cooling
Time
program 5
If the installation is tted with a DHW tank, set the parameter 907 to "Time program 5 / Cooling"
(In order to activate cooling only during the day and leave the DHW system to operate during the night).
Heating Circuit 2
If the installation consists of 2 heating circuits (Only with the 2nd circuit kit option).
1010 Comfort heating setpoint from reduced setpoint to 35°C 0,5 °C 20 °C
1012 Reduced setpoint from frost protection setpoint…
to comfort setpoint
0,5 °C 18 °C
1014 Frost protection setpoint from 4°C… to reduced setpoint 0,5 °C 8 °C
Domestic hot water (DHW) (Only with the DHW kit option)
1610 Nominal setpoint Reduced setting (line 1612)…
to 65 °C
1 50 °C
The backup electrical system is required to reach this level.
1612 Reduced setpoint 8 °C...
to Nominal setpoint (line 1610)
1 25 °C
Swimming pool (Only with swimming pool kit option)
2056 Setpoint source heating 8... 35 °C 22 °C
Fault
6711 Reset HP No, Yes No
Service / Special operation
7141 Emergency operation Off, On Off
Off : The heat pump does not use the backup electrical heating system or the boiler connection when a fault occurs (error 370)
On : The heat pump uses the backup electrical system or the boiler connection when a fault occurs (error 370).
In the "On" position, the energy costs can be onerous if the error is not eliminated.
Operation manual "1328 - EN" - 13 -
Split system