Energy recovery system
Pressure drop, water side
Text on figure
(1) Pressure drop (kPa)
(2) Pressure drop (bar)
(3) Water flow (l/s)
pd = 4.23 F
2
+ 1.62 F
With:
pd = pressure drop in kPa
F = water flow in l/s
The pressure drops calculated with the formulas above are indicative.