Menu's shown on the parameter list LCD:
Genset mode
This menu is used to change the mode of the machine.
In the Qc2002™ module 2 application modes can be
selected:
Island operation
This operation type is selected for local/remote
start applications, without the Mains (= stand-
alone).
Combined with Manual Operation mode =
Local Start operation.
The sequences start / stop / close Generator
Contactor / open Generator Contactor can be
activated manually.
Combined with Automatic Operation mode =
Remote Start operation.
The remote start signal can be given with an
external switch. After the generator has been
started, the Generator Contactor will close
automatically.
Installation wirings for Remote Start operation:
wire the RS switch between X25.9 & X25.10.
Automatic Mains Failure (AMF) operation
When the Mains exceeds the defined voltage /
frequency limits for a defined delay time, the
generator will take over the load automatically.
When the mains is restored within the defined
limits for a defined time, the generator will unload
before disconnecting and switching back to the
Mains.
The generator will then go into cooldown and
stop. It will stay stanby for the next event.
Installation wirings for Remote Start operation:
refer to circuit diagram 9822 0996 06/01 for the
correct connections.
Horn delay
This menu is used to set the delay, how long the
general alarm relay stays energized (if present). If set
to 0.0s, the general alarm relay will stay energized
continuously.
Running hours adjust
This menu is used to adjust the amount of running
hours. The running hours can only be highered, not
lowered.
Service timer 2 reset
Genset Mode
Island Island AMF
This application is only possible in
combination with the AUTO mode.
If the Manual Operation mode is
selected the AMF operation will
NOT function!
To operate the unit in AMF mode,
make sure that the COC (Change
Over Contactors) box is properly
installed, see page 101. Refer to
circuit diagram 9822 0773 55 for the
correct connections.
!
!
Horn Delay
0.0s 20.0s 990.0s
Running Time
Cur. 168 20000
St 2 Reset
No No Yes