- 50 -
If you select SETUP then you get the following view:
The fourth line is the entry selection for the Menu
system. If the SEL button is pressed, the menu
indicated with an underscore will be entered.
If PROT is selected, the following view will appear
(example of parameter):
For a protective function the first entry shows the
“Generator reverse power (G-P>1)” setting.
Scrolling down will give all the protection
parameters:
– The first line shows some generator data.
– The second line shows the channel number and
the name of the parameter.
– The third line shows the value of a set point of this
parameter.
– The fourth line shows the different possible set
points. In this example:
The user can scroll through this list and select one set
point with the SEL button.
After selection of SP the following view will be
visible:
If the correct password is entered, the following view
appears:
Now the user can change the SP of parameter “G-
P>1”. This can be done with the scroll buttons. Then
the user has to select SAVE to save the new settings.
To exit the user has to press the BACK button several
times, until the main view appears.
SP SET POINT, the alarm set point is
adjusted in the set point menu. The setting
is a percentage of the nominal values.
DEL DELAY, the timer setting is the time that
must expire from the alarm level is
reached until the alarm occurs.
OA OUTPUT A, a relay can be activated by
output A.
OB OUTPUT B, a relay can be activated by
output B.
ENA ENABLE, the alarm can be activated or
deactivated. ON means always
activated, RUN means that the alarm
has run status. This means it is activated
when the running signal is present.
FC FAIL CLASS, when the alarm occurs
the unit will react depending on the
selected fail class.