- 62 -
Installations with more generators
(**) The power management system (PMS) allows communication between the Qc4002™ MkII modules over CAN-bus. It has a fully intelligent system, which will start/
load/stop the generator according to the actual load and to the status of each generator. The installation can contain up to 16 Qc4002™ MkII modules. If the Mains is
included in the installation, then an extra Qc4002™ MkII module is required. The installation can be monitored and controlled via the PMS Software Package. For details
on this application, please contact Atlas Copco.
Application type Mode Comments
Island operation
SEMI-AUTO mode = Manual paralleling between generators
AUTO mode = Remote paralleling between generators
AMF operation
(SEMI-AUTO mode) AMF operation will not function properly !
AUTO mode PMS + Qc4002™ MkII Mains module (**)
Peak shaving
SEMI-AUTO mode PMS + Qc4002™ MkII Mains module (**)
AUTO mode PMS + Qc4002™ MkII Mains module (**)
Fixed Power
SEMI-AUTO mode PMS + Qc4002™ MkII Mains module (**)
AUTO mode PMS + Qc4002™ MkII Mains module (**)
Load Take Over
SEMI-AUTO mode PMS + Qc4002™ MkII Mains module (**)
AUTO mode PMS + Qc4002™ MkII Mains module (**)
Main Power Export
SEMI-AUTO mode PMS + Qc4002™ MkII Mains module (**)
AUTO mode PMS + Qc4002™ MkII Mains module (**)
Power Management System
(SEMI-AUTO mode) PMS + Qc4002™ MkII Mains module (**)
AUTO mode PMS + Qc4002™ MkII Mains module (**)