- 22 -
Notes:
(1) V-belt can be ordered with PN 2914 9876 00.
(2) Use PAROIL Extra only.
(3) Rocker cover gaskets can be re-used after valve clearence.
Fuel injectors should be tested every 3000 hrs
Inspect water pump every 3000 hrs
Replace V-belt (1) xx
Measure alternator insulation resistance xx
Check glycol level in coolant xx
Check PH level of engine coolant xx
Check and adjust engine inlet and outlet valves (3) xx
Test glow plugs xx
Check alternator and starter motor x
Test thermostats x
Check engine mounts x
Inspection by Atlas Copco Service technician
Generators in standby application have to be tested on a regular
basis. At least once a month the engine should run for minimum 30
minutes at a high load (50% - 70%) that the engine reaches its
operating temperature.