Supply voltage
(V)
Recommended overload setting F21
(A)
380 187
440 163
460 161
575 127
ZR/ZT 160 compressors designed for a maximum inlet temperature of 40 ˚C/104 ˚F with IE3 motor
Supply voltage
(V)
Recommended overload setting F21
(A)
380 194
440 166
460 163
575 131
ZR/ZT 160 compressors designed for a maximum inlet temperature of 50 ˚C/122 ˚F with IE2 motor
or equipped with oversized IE2 motor
Supply voltage
(V)
Recommended overload setting F21
(A)
380 236
440 204
460 209
575 167
ZR/ZT 160 compressors designed for a maximum inlet temperature of 50 ˚C/122 ˚F with IE3 motor
or equipped with oversized IE3 motor
Supply voltage
(V)
Recommended overload setting F21
(A)
380 219
440 187
460 181
575 146
ZR/ZT 200 compressors designed for a maximum inlet temperature of 40 ˚C/104 ˚F with IE2 motor
Supply voltage
(V)
Recommended overload setting F21
(A)
380 236
440 204
460 209
575 167
ZR/ZT 200 compressors designed for a maximum inlet temperature of 40 ˚C/104 ˚F with IE3 motor
Instruction book
308 2920 1815 04