Byte 27: Out of specification 3
Table 23: Byte 27: Out of specification 3
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
Reserved for future FO cable variant1Warning FO Cable budget
Wrn FO cable budget
0
No signal0
Reserved for future FO cable variant1Warning FOC
Wrn FOC
1
No signal0
Warning: Loss of signal analogue input 21Warning input AIN 2"
Wrn input AIN 2
2
No signal0
Warning: Loss of signal analogue input 11Warning input AIN 1"
Wrn input AIN 1
3
No signal0
Collective signal 15: Internal warning1Internal warning
Internal warning
4
No internal warning0
Warning: Max. number of motor starts (starts) exceeded1Warning On time Starts
Wrn op.mode starts
5
No signal0
Warning: Max. running time/h exceeded1Warning On time Running
Wrn op.mode run time
6
No signal0
Warning: Max. permissible operating time for an operation
(OPEN-CLOSE) exceeded
1Operation time warning
Op. time warning
7
No signal0
Byte 28: Out of specification 4
Table 24: Byte 28: Out of specification 4
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
No signal (reserved)——0
No signal (reserved)——1
Warning: Loss of signal of actuator setpoint position1Warning setpoint position
Wrn setpoint position
2
No signal0
Warning: A Partial Valve Stroke Test (PVST) should be
performed.
1PVST required
PVST required
3
0
Reserved for future FO cable variant1Warning FOC connection
Wrn FOC connection
4
No signal0
The failure behaviour is active.1Failure behaviour active
Failure behav. active
5
No signal0
Partial Valve Stroke Test (PVST) was aborted or could
not be started. Remedy: Perform RESET or restart PVST.
1PVST abort
PVST abort
6
No signal0
Partial Valve Stroke Test (PVST) could not be successfully
completed.
1PVST fault
PVST fault
7
No signal0
Byte 29: Function check 1
Causes of the Function check signal in accordance with NAMUR recommendation
NE 107.
28
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profinet