Table 21: Byte 25: Out of specification 1
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
No signal (reserved)0
No signal (reserved)1
No signal (reserved)2
FQM Fail Safe fault active:
- "FQM FS-Ready" not ready although "FQM FS-Esd-
Active" not active
- "FQM FS-Ready" ready although "FQM FS-Esd-Active"
active
- "FQM-Timeout-Tension" active
- "FQM-Timeout-Limit" aktiv
FQM fail safe fault
3
Warning: Limit value for torque warning in direction
CLOSE exceeded.
1Torque warning CLOSE
Torque wrn CLOSE
4
No signal0
Warning: Limit value for torque warning in direction OPEN
exceeded.
1Torque warning OPEN
Torque wrn OPEN
5
No signal0
Warning: A SIL fault of the SIL sub-assembly has oc-
curred.
1SIL fault
SIL fault
1)
6
No signal0
Warning: No actuator reaction to operation commands
within the set reaction time.
1Warning no reaction
Wrn no reaction
7
No signal0
The safety function indications via communication interface are for information only and must not be used as part of a safety function.
The I/O signals of the SIL module must be used for this purpose.
1)
Byte 26: Out of specification 2
Table 22: Byte 26: Out of specification 2
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
Warning: Temperature within actuator controls housing
too high.
1Warning controls temperat-
ure
Wrn controls temp.
0
No signal0
Warning gearbox temperature1
Wrn gearbox temp.
1
No signal0
Warning motor temperature1
Wrn motor temp.
2
No signal0
The external 24 V DC voltage supply of the controls has
exceeded the power supply limits.
124 V DC, external
24 V DC external
3
No signal0
No signal (reserved)4
Warning: Voltage of RTC button cell too low.1RTC button cell
RTC voltage
5
No signal0
The real time clock has not yet been set on the basis of
valid values.
1RTC not set
Time not set
6
No signal0
Warning: Configuration setting is incorrect.
The device can still be operated with restrictions.
1Configuration warning
Config. warning
7
No signal0
27