Bytes 21 and 22: Input AIN 2
Byte 21 = high byte, byte 22 = low byte.
In Byte 9 und Byte 10 wird der Wert des zweiten, zusätzlichen freien analogen
Stromeingangs der Profinet Schnittstelle übertragen. Die Anfangs- und Endwerte
können an der AC über die Drucktaster und das Display eingestellt werden. (For
operation, please refer to the respective operation instructions for the actuator.)
If the measuring values are 0.3 mA below the initial value, a signal loss is indicated.
Der Wert wird in Promille (Wert: 0 1000) übertragen.
Byte 23: Failure
Causes of the Failure signal in accordance with NAMUR recommendation NE 107.
Table 19: Byte 23: Failure
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
No signal (reserved)0
No signal (reserved)1
No signal (reserved)2
No signal (reserved)3
No signal (reserved)4
No signal (reserved)5
No signal (reserved)6
Collective signal 03:
Contains the result of a disjunction (OR-operation) of all
bits of bytes 15 and 16 (Fault 1 and Fault 2).
The actuator cannot be operated.
1Fault
Fault
7
In bytes 15 and 16, no faults are active (all bits are set to
0).
0
Byte 24: Maintenance required
Causes of the Maintenance required signal in accordance with NAMUR
recommendation NE 107.
Table 20: Byte 24: Maintenance required
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
Mechanic maintenance requirement (AUMA service)1Maintenance mechanics
Mainten. mechanics
0
No signal0
Seal maintenance requirement (AUMA service)1Maintenance seals
Mainten. seals
1
No signal0
Lubricant maintenance requirement (AUMA service)1Maintenance lubricant
Mainten. lubricant
2
No signal0
Contactor maintenance requirement (AUMA service)1Maintenance contactors
Mainten. contactors
3
No signal0
The set maintenance interval has expired.1Maintenance interval
Mainten. interval
4
No signal0
No signal (reserved)5
No signal (reserved)6
No signal (reserved)7
Byte 25: Out of specification 1
Causes of the Out of specification signal in accordance with NAMUR recommendation
NE 107.
26
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profinet