DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
The real time clock has not yet been set on the basis of
valid values.
1RTC not set
Time not set
6
No signal0
Warning: Configuration setting is incorrect.
The device can still be operated with restrictions.
1Configuration warning
Config. warning
7
No signal0
Byte 19:Warnings 3
Table 17: Byte 19: Warnings 3
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
Warning: FO cable system reserve reached (critical or
permissible Rx receive level)
1Warning FO cable budget
Wrn FO cable budget
0
No signal0
Warning:
Optical receiving signal (channel 1) incorrect (no or insuf-
ficient Rx receive level) or RS-485 format error.
1Warning FOC
Wrn FOC
1
No signal0
Warning: Loss of signal analogue input 21Warning Input AIN 2
Wrn input AIN 2
2
No signal0
Warning: Loss of signal analogue input 11Warning Input AIN 1
Wrn input AIN 1
3
No signal0
Collective signal 15: Internal warning1Internal Warning
Internal warning
4
No internal warning0
Warning: Max. number of motor starts (starts) exceeded1Warning On time Starts
Wrn op.mode starts
5
No signal0
Warning: Max. running time/h exceeded1Warning On time Running
Wrn op.mode run time
6
No signal0
Warning: Max. permissible operating time for an operation
(OPEN-CLOSE) exceeded
1Operation time warning
Op. time warning
7
No signal0
Byte 20:Warnings 4
Table 18: Byte 20: Warnings 4
DescriptionValuePrm-Text-Def GSD fileDesignation
(process representation)
Bit
No signal (reserved)0
No signal (reserved)1
Warning: Loss of signal of actuator setpoint position1Warning Setpoint position
Wrn setpoint position
2
No signal0
Warning: A Partial Valve Stroke Test (PVST) should be
performed.
1PVST required
PVST required
3
0
Warning: FOC connection is not available.1Warning FOC connection
Wrn FOC connection
4
No signal0
The failure behaviour is active.1Failure behaviour actice
Failure behav. active
5
No signal0
Partial Valve Stroke Test (PVST) was aborted or could
not be started. Remedy: Perform RESET or restart PVST.
1PVST abort
PVST abort
6
No signal0
Partial Valve Stroke Test (PVST) could not be successfully
completed.
1PVST fault
PVST fault
7
No signal0
25
Actuator controls
AC 01.2/ACExC 01.2 Profinet Description of the data interface