As an alternative, the process setpoint can be transmitted via bytes 3 and 4 (value
0...1,000), using a process controller (option).Value 1,000 corresponds to the
maximum process setpoint, value 0 to the minimum process setpoint.
Byte 5: Additional commands
Table 29: Byte 5: Additional commands
DescriptionValueDesignation
(process representation)
Bit
Actuator operation via local controls enabled1
Fieldb. enable LOCAL
0
Actuator operation via local controls disabled0
Enables operation command in direction OPEN1
Fieldb. enable OPEN
1
Operation command in direction OPEN disabled.0
Enables operation command in direction CLOSE1
Fieldb. enable CLOSE
2
Operation command in direction CLOSE disabled.0
No command (reserved)—3
Initiate change-over to channel 11
Fieldbus channel 1
4
No operation command0
No command (reserved for future variants)1
Fieldbus channel 2
5
No operation command0
EMERGENCY signal, triggers EMERGENCY beha-
viour.
1
Fieldbus EMCY
6
No command0
Start Partial Valve Stroke Test (functional test)1
PVST
7
No operation command0
Byte 6: Intermediate positions
Table 30: Byte 6: Intermediate positions
DescriptionValueDesignation
(process representation)
Bit
Run to intermediate position 1.1
Intermediate pos. 1
0
No command0
Run to intermediate position 2.1
Intermediate pos. 2
1
No command0
Run to intermediate position 3.1
Intermediate pos. 3
2
No command0
Run to intermediate position 4.1
Intermediate pos. 4
3
No command0
Run to intermediate position 5.1
Intermediate pos. 5
4
No command0
Run to intermediate position 6.1
Intermediate pos. 6
5
No command0
Run to intermediate position 7.1
Intermediate pos. 7
6
No command0
Run to intermediate position 8.1
Intermediate pos. 8
7
No command0
Bits 0 – 7 allow the direct selection of 8 intermediate positions via fieldbus commands.
Hereby the selected intermediate position is approached directly, without stopping
in another intermediate position.
In this case, the actuator continues running until the selected intermediate position
has been reached. Example: Operation from position 5 to 7 without stopping at
position 6.
For further information, please refer to the AUMATIC AC 01.2 Profinet manual
(operation and setting).
33
Actuator controls
AC 01.2/ACExC 01.2 Profinet Description of the data interface