If the multiport valve function is active (option), the entire byte 6 is used for coding
of multiport valve operation commands. Up to 16 positions can either be approached
selecting the shortest travel, in clockwise direction (CW), or in counterclockwise
direction (CCW). Furthermore, the actuator can also be operated without any position
indications in clockwise or counterclockwise direction (CW or CCW).
Table 31: Operation commands via byte 6 for activated multiport valve function
Behaviour
≙ Operation direction/posi-
tion
Value
Position 1 is approached selecting the shortest
travel
Position 1
0x01
Position 2 is approached selecting the shortest
travel
Position 2
0x02
Position 3 is approached selecting the shortest
travel
Position 3
0x04
Position 4 is approached selecting the shortest
travel
Position 4
0x08
Position 5 is approached selecting the shortest
travel
Position 5
0x10
Position 6 is approached selecting the shortest
travel
Position 6
0x20
Position 7 is approached selecting the shortest
travel
Position 7
0x40
Position 8 is approached selecting the shortest
travel
Position 8
0x80
Position 9 is approached selecting the shortest
travel
Position 9
0x81
Position 10 is approached selecting the shortest
travel
Position 10
0x82
Position 11 is approached selecting the shortest
travel
Position 11
0x83
Position 12 is approached selecting the shortest
travel
Position 12
0x84
Position 13 is approached selecting the shortest
travel
Position 13
0x85
Position 14 is approached selecting the shortest
travel
Position 14
0x86
Position 15 is approached selecting the shortest
travel
Position 15
0x87
Position 16 is approached selecting the shortest
travel
Position 16
0x88
Actuator operates in clockwise direction (without
stop at any position).
CW
0x90
Position 1 is approached in clockwise direction
(CW).
CW Position 1
0x91
Position 2 is approached in clockwise direction
(CW).
CW Position 2
0x92
Position 3 is approached in clockwise direction
(CW).
CW Position 3
0x93
Position 4 is approached in clockwise direction
(CW).
CW Position 4
0x94
Position 5 is approached in clockwise direction
(CW).
CW Position 5
0x95
Position 6 is approached in clockwise direction
(CW).
CW Position 6
0x96
Position 7 is approached in clockwise direction
(CW).
CW Position 7
0x97
Position 8 is approached in clockwise direction
(CW).
CW Position 8
0x98
Position 9 is approached in clockwise direction
(CW).
CW Position 9
0x99
34
Actuator controls
Description of the data interface AC 01.2/ACExC 01.2 Profinet