Table 82: Asset Management > Operational info total
ExplanationSetting valueDefaultAc-
cess
ParametersTypeID
Data length = 80 bytes
Motor running time throughout
the lifetime
Min = 0 [s]R
Motor running time
MMSS01495PRM
Max = 4294967295 [s]
Min = 0 [s]R
Max. running time/h
MMSS015227PRM
Max = 4294967295 [s]
Operating hours counter: num-
ber of hours during which con-
trols are supplied with power
Min = 0 [s]R
Operating hours
MMSS015068PRM
Max = 4294967295 [s]
Number of motor starts
throughout the lifetime
Min = 0 [s]R
Motor starts
U32496PRM
Max = 4294967295 [s]
Min = 0R
Max. starts/h
U325226PRM
Max = 4294967295
Min = 0 [%]R
Mean torque value
U325213PRM
Max = 4294967295 [%]
Number of thermal faults
throughout the lifetime
Min = 0R
No. thermal faults
U32503PRM
Max = 4294967295
Number torque faults CLOSE
throughout the lifetime
Min = 0R
Torque fault CLOSE
U32501PRM
Max = 4294967295
Number of torque faults OPEN
throughout the lifetime
Min = 0 [s]R
Torque fault OPEN
U32502PRM
Max = 4294967295 [s]
Number of torque warnings
OPEN+CLOSE during the life-
time
Min = 0R
Wrn torque CLOSE
U324704PRM
Max = 4294967295
Number of torque warnings
OPEN+CLOSE during the life-
time
Min = 0R
Wrn torque OPEN
U324703PRM
Max = 4294967295
Number of torque warnings
OPEN+CLOSE during the life-
time
Min = 0R
Wrn torque OP+CL
U325401PRM
Max = 4294967295
Number of limit switch CLOSE
trippings throughout the lifetime
Min = 0R
Limit trip CLOSE
U32498PRM
Max = 4294967295
Number of limit switch OPEN
trippings throughout the lifetime
Min = 0R
Limit trip OPEN
U32500PRM
Max = 4294967295
Number of torque switch
CLOSE trippings throughout the
lifetime
Min = 0R
Torque trip CLOSE
U32497PRM
Max = 4294967295
Number of torque switch OPEN
trippings throughout the lifetime
Min = 0R
Torque trip OPEN
U32499PRM
Max = 4294967295
Total number of all time intervals
throughout the lifetime during
which an on time warning was
indicated.
Min = 0 [s]R
On time warning 1
U32505PRM
Max = 4294967295 [s]
Max. time span during which an
on time warning was indicated.
Min = 0 [s]R
On time warning 2
U32506PRM
Max = 4294967295 [s]
Number of system starts
throughout the lifetime
Min = 0R
No. system starts
U32507PRM
Max = 4294967295
Maximum temperature of con-
trols
Min = –100 [°C]R
Max. temp. controls
I324765PRM
Max = +150 [°C]
Minimum temperature of con-
trols
Min = –100 [°C]R
Min. temp. controls
I324766PRM
Max = +150 [°C]
Maximum temperature of MWG
Min = –100 [°C]R
Max. temp. MWG
I324771PRM
Max = +150 [°C]
65
Actuator controls
AC 01.2/ACExC 01.2 Profinet Appendix